Dear Customer,
Enclosed you will find the RFO report from our data center and its feedback to us.
Dear Customer,
After careful analysis, we would like to comment on the incident that occurred on March 12, 2025, in FRA1. After the incident was resolved, a thorough and comprehensive analysis was conducted. The associated incident report is attached .
If you have any further questions, please do not hesitate to contact us.
We would like to apologize for any inconvenience and deeply regret this incident.
Thank you for your understanding.
Best regards
- ResolvedResolved
The data center was able to resolve the remaining issues with the rack, and the power connection has now been fully restored. The last issues were due to a switch issue, which is now also functioning correctly again.
We have restarted all customer systems and our monitoring no longer reports any problems.
If any of your services are not working, please contact us.
We would like to take this opportunity to apologize again for any inconvenience caused.
As soon as we receive the RFO report from the data center, we will publish it here.
- UpdateUpdate
Dear customers,
Unfortunately, some customer systems are still affected.
We deeply regret this and are in close contact with the data center to restore your services as quickly as possible.
We have just received the following update from Frankfurt:
Dear customers,
During the announced maintenance work, an unexpected power outage occurred today in our data center rooms R1 and R2 at the FRA1 location. In order to be able to carry out the announced maintenance work on the UPS, additional protective measures have been taken to further safeguard against any impact on customer infrastructures.
During the initiation of maintenance measures, the active systems were diverted to redundant systems. During the switchover and initiation of parallel feed-in, a short circuit occurred between two phases, triggered by a technical defect. The short circuit caused the relevant fuses to trip properly.
The emergency process was initiated immediately, and an initial fault analysis was conducted. The fault was quickly identified, and power restoration was initiated immediately. Due to this incident, all further maintenance work was halted.
We deeply regret the disruption and will address it internally and make appropriate improvements. Thank you for your understanding.
- MonitoringMonitoring
We received the following additional feedback from the data center:
Power has been restored. Our systems are back up and will be fully operational shortly.
The systems of Quality Location and its customers are partially active again.
We ask for your patience until all systems are fully available.
- IdentifiedIdentified
Dear customers,
The following feedback was received from the data center team.
Ladies and Gentlemen
We would like to inform you that there is currently a technical issue at our R1 and R2 locations. Our technicians are working with the highest priority to identify the cause and resolve the issue as quickly as possible.
The exact duration of the outage cannot yet be estimated. We will provide further details about the incident and the expected resolution time shortly.
There are limitations in availability, redundancy and performance in the areas of networking and object storage.
As soon as we have further information, we will publish it immediately.
- InvestigatingInvestigating
Dear customers,
We are currently experiencing isolated downtimes of our infrastructure and customer systems in our racks.
Technicians are currently investigating the issue.
As soon as we have further information, we will share it immediately.Thank you for your understanding